Model No.︰P400
Brand Name︰dk power diesel generators
Country of Origin︰China
Unit Price︰-
Minimum Order︰1 pc
500kva prime power,550 kva standby power, Perkins diesel generators adopted Perkins diesel engine 2506C-E15TAG2 and stamford HCI544D alternator.
Technical Data |
|||||
GENSETS
|
Manufacturer
|
DK POWER
|
|||
Model
|
P400
|
||||
Frequency
|
50HZ
|
||||
Power
|
Standby Power
|
440KW 550KVA
|
|||
Prime Power
|
400KW 500KVA
|
||||
Size
|
Dimension(L*W*H)
|
Open -mm
|
3900×1150×2100
|
||
Dimension(L*W*H)
|
Canopy mm
|
5230×1380×2200
|
|||
DIESEL ENGINE
|
Engine Manufacturer
|
Perkins
|
|||
Model
|
2506C-E15TAG2
|
||||
Cylinder Arrangement
|
6 in line
|
||||
Cycle
|
4 stroke
|
||||
Aspiration
|
Turbocharged air-air cooled
|
||||
Bore×Stroke (mm×mm)
|
137 x 171
|
||||
Displacement(Liter)
|
15.2
|
||||
Compression Ratio
|
16:1
|
||||
Prime Power/Speed (kW/rpm)
|
435/1500
|
||||
Standby Power/Speed (kW/rpm)
|
478/1500
|
||||
Speed Governor
|
Electrical
|
||||
Cooling System
|
Water-cooled
|
||||
Total lubrication system capacity (L)
|
62
|
||||
Coolant capacity (inc. radiator) (L)
|
58
|
||||
Fuel Consumption at 100% Load (g/kWh)
|
211(at 1500RPM)
|
||||
Alternator
|
Manufacturer
|
Stamford
|
|||
Model
|
HCI544D
|
||||
Rated Voltage
|
230/400V
|
||||
Voltage regulation mode
|
Auto
|
||||
Exciter Type
|
Brushless self exciting
|
||||
Power factor
|
0.8
|
||||
Capacity (Kva)
|
550
|
||||
Insulation class
|
H
|
||||
Protection class
|
IP23
|
Data list with UK Perkins Engines ,Stamford Alternator
Payment Terms︰ 30% T/T down payment,balance 70% before shipment