600kva prime,660 kva standby Perkins diesel generators adopted Perkins diesel engine 2806A(C)-E18TAG1A and stamford HCI544E alternator.
Technical Data |
|||||
GENSETS
|
Manufacturer
|
DK POWER
|
|||
Model
|
P480
|
||||
Frequency
|
50HZ
|
||||
Power
|
Standby Power
|
528KW 660KVA
|
|||
Prime Power
|
480KW 600KVA
|
||||
SIZE
|
Dimension(L*W*H)
|
Open mm
|
3700×1600×2200
|
||
Dimension(L*W*H)
|
canopy
|
20GP
|
|||
DIESEL ENGINE
|
Engine Manufacturer
|
Perkins
|
|||
Model
|
2806A-E18TAG1A
|
||||
Cylinder Arrangement
|
6 in line
|
||||
Cycle
|
4 stroke
|
||||
Aspiration
|
Turbocharged air-air cooled
|
||||
Bore×Stroke (mm×mm)
|
145 x 183
|
||||
Displacement(Liter)
|
18.1
|
||||
Compression Ratio
|
14.5:1
|
||||
Prime Power/Speed (kW/rpm)
|
522/1500
|
||||
Standby Power/Speed (kW/rpm)
|
574/1500
|
||||
Speed Governor
|
Electrical
|
||||
Cooling System
|
Water-cooled
|
||||
Total lubrication system capacity (L)
|
62
|
||||
Coolant capacity (inc. radiator) (L)
|
61
|
||||
Fuel Consumption at 100% Load (g/kWh)
|
203(at 1500RPM)
|
||||
Alternator
|
Manufacturer
|
Stamford
|
|||
Model
|
HCI544E
|
||||
Rated Voltage
|
230/400V
|
||||
Voltage regulation mode
|
Auto
|
||||
Exciter Type
|
Brushless self exciting
|
||||
Power factor
|
0.8
|
||||
Capacity (Kva)
|
610
|
||||
Insulation class
|
H
|
||||
Protection class
|
IP23
|